TYPE AND QUANTITY OF FIRE EXTINGUISHING APPLIANCES
AS REQUIRED BY REGULATION 9(1)
Type
Minimum
capacity
per
appliance
Quantity
1.
Bucket (galvanised iron) of sand
AND
9 litres
2
2.
(a) Bromochlorodifluoromethane
(B.C.F.)

or
1.4 kg
    1 for every room or area of 40 square metres or less.
(b) Carbon dioxide

or
2 kg
    1 for every room or area of 33 square metres or less.
(c) Dry powder (gas expelled)

or
2 kg
    1 for every room or area of 33 square metres or less.
(d) Foam (chemical)
9 litres
    1 for every room or area of 40 square metres or less.