Hong Kong Regulations
[Index]
[Table]
[Search]
[Notes]
[Noteup]
[Previous]
[Next]
[Download (Current & Past)]
[Download (Current only)]
[繁體中文]
[Help]
FACTORIES AND INDUSTRIAL UNDERTAKINGS (SPRAYING OF FLAMMABLE LIQUIDS) REGULATIONS - REGULATION 4
Construction of spraying room or spraying area etc.
PART II
DUTIES OF PROPRIETORS
(1) No flammable liquid spraying process shall be carried on except in-
(a) a spraying room constructed of materials-
(i) in the case of floors, walls and ceilings, having an F.R.P. of
not less than 1 hour; and
(ii) in the case of windows and doors, being capable of resisting
the action of fire for a period of not less than 1/2 hour and
complying with the specifications set forth in *Tables F and G
respectively in the Third Schedule to the
Building (Construction) Regulations ( Cap 123 sub. leg. C); or
(b) a spraying area set aside for the purpose, and then only if the
spraying process is carried on inside a booth or cabinet which is
completely enclosed except in so far as openings are necessary to
enable the work to be carried out or for ventilation purposes as
required by regulation 5.
(2) All ducts, trunking, hoods, booths, cabinets and casings provided or used
in connexion with a flammable liquid spraying process shall be capable of
resisting the action of fire for a period of not less than 1/2 hour.
___________________________________________________________________ Note:
* See Cap 123 sub. leg. B, 1985 Edition.
[Index]
[Table]
[Search]
[Notes]
[Noteup]
[Previous]
[Next]
[Download (Current & Past)]
[Download (Current only)]
[繁體中文]
[Help]