ELECTRICITY SUPPLY REGULATIONS - REGULATION 37
Connection with earth of a three-wire system
CONNECTION OF CIRCUITS WITH EARTH
Where the pressure of a supply between the adjacent conductors of a three-wire
system of mains exceeds 125 volts the intermediate conductor shall be
connected with earth in accordance with the following conditions-
(a) the connection with earth of the intermediate conductor shall be made
at 1 point only on each distinct circuit, namely at the generating
station, sub-station or transformer, and the insulation of the circuit
shall be efficiently maintained at all other parts;
(b) the current from the intermediate conductor to earth shall be
continuously recorded and if it at any time becomes excessive steps
shall be immediately taken to improve the insulation of the system.